Enter voltage and current phase angles (degrees) for each phase. Uses ±180° convention per NASPI TR-006.
When on, suggests positive/negative CT (reversed polarity) when V−I angle is near ±180°.
Optional. Used for multiplier and to tailor fix suggestions (e.g. “set CT ratio to 100:5”).
Phase angle φ = I − V (phasor difference). Power factor pf = cos(φ). Per phasor convention: positive φ = current lags voltage (inductive); negative φ = current leads voltage (capacitive). Resistive: φ ≈ 0°.
V∠θ; lead = +θ, lag = −θ; CCW, 0° = real axis.pf = cos(φ), φ = cos⁻¹(pf); φ = tan⁻¹(X/R); φ = 360°×(Δt/T).
Per phasor convention: each quantity is a phasor (magnitude ∠ phase); 0° = right (real axis), CCW = positive angle.
| Phase | V entered | I entered | V norm | I norm | V–I angle (PF) |
|---|
Angles: Subtract then wrap to (−180°, 180°] (phasor angle difference; phasors, phase & phasors). Phase sequence: We expect ABC (positive sequence): Va reference 0°, Vb ≈ −120° (lagging), Vc ≈ +120°; so Vb−Va ≈ −120°, Vc−Va ≈ +120°. ACB (negative sequence) gives Vb−Va ≈ +120°, Vc−Va ≈ −120°. CW/CCW can mean motor rotation (NJIT Lab 3: abc = CW positive, acb = CCW negative) or phasor diagram (EEP: ABC = CCW, ACB = CW)—conventions vary. Phase sequence affects motor direction, paralleling transformers, and two-wattmeter method.